Technical Data: KFD0-TR-Ex1
General specifications | ||
Signal type | Analog input | |
Supply | ||
Rated voltage | 12 ... 35 V DC loop powered | |
Power loss | 0.4 W | |
Input | ||
Connection | terminals 1, 2-, 3+ suitable for Pt100, 2- and 3-wire connection | |
Lead resistance | max. 100 Ω per lead | |
Measuring current | approx. 1 mA | |
Output | ||
Connection | terminals 9+, 8- | |
Load | (U -12 V) / 0.02 A | |
Current output | 4 ... 20 mA , limited to ≤ 35 mA | |
Fault signal | upscaling ≥ 22 mA (limited to 35 mA) | |
Transfer characteristics | ||
Measurement range | span without linearization 25 ... 800 °C (77 ... 1472 °F)/with linearization 25 ... 375 °C (77 ... 707 °F), both adjustable zero point without linearization -200 ... 400 °C (-328 ... 752 °F)/with linearization -30 ... 375 °C (-22 ... 707 °F), both adjustable |
|
Rise time | 250 ms | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Conformity | ||
Insulation coordination | EN 50178 | |
Electrical isolation | EN 50178 | |
Electromagnetic compatibility | NE 21 | |
Protection degree | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Protection degree | IP20 | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2 | |
Data for application in connection with Ex-areas | ||
EC-Type Examination Certificate | ZELM 00 ATEX 0036 , for additional certificates see www.pepperl-fuchs.com | |
Group, category, type of protection | II (1)GD [EEx ia] IIC | |
Statement of conformity | TÜV 01 ATEX 1777X , observe statement of conformity | |
Group, category, type of protection, temperature class | II 3G Ex nA II T4 | |
Directive conformity | ||
Directive 94/9/EC | EN 50014, EN 50020 , EN 60079-0:2006, EN 60079-15:2005 | |
International approvals | ||
CSA approval | ||
Control drawing | 116-0132 |